Heating Power Calculator

Enter flow and ΔT to get thermal power in kW, BTU/h and tons — with the hydronic shortcut (kW ≈ L/min × ΔT ÷ 14.3) built in.

Heating Power Calculator inputs

Last updated: 2026-09-28

How the calculation works

  • Mass flow (flow × density) times specific heat times ΔT gives kilowatts directly.
  • Glycol mixtures carry less heat per litre — the fluid selector applies their real c and ρ.
  • BTU/h and tons conversions connect to US equipment ratings.

Formula

Q = ṁ · c · ΔT        (ṁ = flow × density)
Formula variables
SymbolMeaningUnit
QThermal powerkW
ṁMass flowkg/s

Worked example

A boiler circulating 20 L/min with a 10 °C rise: Q = (20/60) × 998 × 4.186 × 10 / 1000 = 13.9 kW (47,500 BTU/h). The hydronic shortcut: 20 × 10 ÷ 14.3 = 14.0 kW — same answer, no calculator needed.

Interpreting the result

This equation runs both directions: pick two of (flow, ΔT, power) and the third follows. A chiller delivering 20 kW at 5 °C design ΔT needs 57 L/min — undersized flow shows up as a bigger ΔT and poor heat exchange. Glycol costs capacity: a 50% mix needs ~20% more flow for the same duty, which is why glycol systems upsize pumps as well as checking freeze protection.

Assumptions

  • Steady flow, no phase change, fluid properties at operating temperature.
  • Densities: water 998, 30% glycol 1038, 50% glycol 1062, oil 870 kg/m³.

Limitations

  • Steam systems (phase change) need latent-heat math, not this sensible model.
  • Does not size the equipment — it converts measured flow/ΔT into duty (or vice versa).

Frequently asked questions

How do I calculate boiler kW from flow and temperature?

kW = flow(L/min) × ΔT(°C) ÷ 14.3 for water. 20 L/min heated 10 °C ≈ 14 kW — verify by measuring both sides of the boiler.

Why does glycol reduce heating capacity?

Glycol is thicker and carries less heat per litre: a 50% mix has ~26% less heat capacity than water. The same pump and coil deliver proportionally less duty.

Related tools

Technical references