Breaker Size Calculator

Enter the load current and whether it's continuous to get the design current and the next standard breaker rating — plus the conductor requirement that goes with it.

Breaker Size Calculator inputs

Last updated: 2026-09-15

How the calculation works

  • Continuous loads (3 h+) multiply by 1.25 per NEC 210.20(A) so the breaker doesn't sit at 100% for hours.
  • The design current is matched to the next standard rating from the 15–400 A series.
  • The conductor must have ampacity (after derating) at least equal to the design current.

Formula

Design A = load × 1.25 (continuous)
Breaker = next standard rating ≥ design current
Formula variables
SymbolMeaningUnit
I_designDesign currentA
I_breakerStandard breaker ratingA

Worked example

A 24 A water heater (continuous): design = 30 A → 30 A breaker and conductors with ≥30 A derated ampacity (10 AWG copper at 75 °C).

Interpreting the result

The breaker protects the conductor, not the appliance — so conductor and breaker size together. Going one breaker size up without upsizing the wire is the classic code violation. Standard ratings exist because devices are manufactured in fixed sizes; the next-size-up rule (240.4(B)) has strict conditions.

Assumptions

  • General branch-circuit rules; motor circuits follow NEC 430 with different multipliers.
  • Standard thermal-magnetic breaker trip characteristics.

Limitations

  • Motor branch/short-circuit protection can be 2.5× FLC (inverse-time) — this tool is not for motor circuits.
  • Specific appliance rules (AC units, ranges) override general sizing.

Frequently asked questions

What breaker for a 20 amp load?

A 20 A breaker for non-continuous; if it runs 3+ hours, 25 A design → 25 A breaker with matching conductor.

Can I use a bigger breaker than the wire rating?

Generally no — the breaker protects the wire. Limited exceptions exist (240.4(B) next-size-up, motor circuits), but they're rule-specific, not general.

Related tools

Technical references