Heating Load Calculator

Size a heater from floor area, indoor-outdoor design temperature difference and envelope insulation quality, with the U-factor model documented.

Heating Load Calculator inputs

Indoor design temp minus outdoor design temp. E.g. 70 °F indoors, 10 °F design outdoor = 60 °F.

Last updated: 2026-09-15

How the calculation works

  • The envelope is reduced to a single U factor based on insulation quality: 0.06 (good), 0.08 (average), 0.12 (poor) BTU/h·ft²·°F.
  • Load = area × U × design ΔT gives the heat needed to hold the indoor design temperature at the outdoor design temperature.
  • The result is converted to kW for comparison with electric heaters and heat pump ratings.

Formula

Load = Area × U × ΔT
U = overall envelope heat-transfer coefficient (BTU/h·ft²·°F)
Formula variables
SymbolMeaningUnit
UWhole-envelope U factorBTU/h·ft²·°F
ΔTDesign temperature difference°F
AreaConditioned floor areaft²

Worked example

A 1,000 ft² house with average insulation in a climate with a 60 °F design ΔT: 1,000 × 0.08 × 60 = 4,800 BTU/h envelope loss. Adding ~10% for infiltration gives ≈ 5,300 BTU/h ≈ 1.6 kW — a small heat pump or 5–6 kW electric heater.

Interpreting the result

The result is the heat input needed at design conditions — the coldest reasonable weather, not the absolute record. Equipment should be sized near this figure; much larger furnaces short-cycle and cost more. Heat pumps should be checked against their capacity at the local design temperature, not their 47 °F rating.

Assumptions

  • Whole-envelope U factor lumping walls, roof, floor and glazing into one coefficient.
  • Design conditions per local climate data, not extreme records.

Limitations

  • No infiltration/ventilation included — add roughly 10% for typical airtightness, more for fireplaces or leaky older homes.
  • Not valid for passive-solar or high-performance envelopes with U below 0.04.
  • Use Manual J for final equipment selection.

Frequently asked questions

How do I find my design temperature difference?

Take your indoor design temperature (typically 68–70 °F / 20 °C) and subtract the 99th-percentile winter design temperature for your location, published by ASHRAE or your national weather service.

Should I oversize my furnace?

No — size to the calculated load with a small margin. Oversized furnaces short-cycle, waste energy and create uneven temperatures.

Related tools

Technical references