HVAC & Climate · Engineering calculator

Sensible Heat & Airflow Calculator

Work with the core air-side equation Q = 1.08 × CFM × ΔT: enter two values to get the third, with metric conversions and typical target airflows.

Open calculator
Engineering calculatorSensible Heat & Airflow Calculator
Sensible Heat & Airflow Calculator inputs

Leave exactly one field blank to solve for it.

Last updated: 2026-09-15

How the calculation works

  • The 1.08 factor bundles air density (0.075 lb/ft³) and specific heat (0.24 BTU/lb·°F) with the 60 min/h conversion.
  • Leave one field blank to solve for it: airflow needed, heat delivered, or the resulting ΔT.
  • The tonnage equivalent connects the answer to equipment sizing.

Worked example

A 2-ton (24,000 BTU/h) system with a 20 °F design ΔT: CFM = 24,000 ÷ (1.08 × 20) = 1,111 CFM — 370 CFM/ton, right in the normal range. If the blower only delivers 800 CFM, the same heat gives ΔT = 27.8 °F: colder supply air, poorer mixing.

Interpreting the result

This equation is the air-side heartbeat of HVAC: given equipment capacity and airflow it fixes the supply-to-return temperature split. Low airflow (clogged filter, weak blower) shows up as high ΔT, frozen coils in cooling, and heat exchanger stress in heating. Designers use 350–450 CFM per ton for cooling.

Assumptions

  • Standard air at sea level — high altitude needs a corrected factor (1.08 × density ratio).
  • Sensible heat only; latent (moisture) heat needs a separate wet-coil calculation.

Limitations

  • Wet-coil (cooling with dehumidification) conditions need the total heat formula including latent load.
  • High-altitude installations must correct for air density.

Sensible cooling (BTU/h) by airflow and temperature difference

Airflow15 °F ΔT18 °F ΔT20 °F ΔT25 °F ΔT
400 CFM6,4807,7768,64010,800
800 CFM12,96015,55217,28021,600
1,200 CFM19,44023,32825,92032,400
1,600 CFM25,92031,10434,56043,200

Q = 1.08 × CFM × ΔT for standard air. A ton of cooling is 12,000 BTU/h.

Worked scenario: how much air does a 2-ton system need?

A 24,000 BTU/h load with a 20 °F temperature drop across the coil needs 1,111 CFM of sensible capacity. Going the other way, 800 CFM at the same ΔT carries 17,280 BTU/h, or 1.44 tons.

Limits of the equation

  • It covers sensible heat only. Removing moisture (latent heat) is separate, so total cooling is higher.
  • The 1.08 factor assumes standard air at sea level. At high altitude the air is thinner and the factor drops.
  • Real systems are specified at a design ΔT, which depends on the equipment and the humidity of the climate.

Frequently asked questions

What CFM per ton should I have?

350 CFM/ton in humid climates (better dehumidification), 400 in moderate, up to 450 in dry climates. Outside that range, check airflow and charge.

Why is my ΔT too high?

Usually low airflow — dirty filter, failing blower, or blocked returns. In heating, an over-fired furnace shows the same symptom.

Related tools

Technical references