Transformer Sizing Calculator
Enter load kW, PF and voltages to get the required kVA with margin, plus primary and secondary currents for protection sizing.
Open calculatorLast updated: 2026-09-15
How the calculation works
- Load kW converts to kVA through the power factor — transformers are rated in kVA because heating depends on current, not phase.
- The margin inflates the requirement for continuous loads and future growth.
- Primary and secondary currents follow from the same kVA at each voltage, for conductor and protection sizing.
Worked example
Interpreting the result
Transformers are rated in kVA, not kW, because their heating depends on current regardless of the load's power factor. A low-PF load forces a bigger transformer for the same useful power — another reason PF correction pays. Standard sizes exist at 15, 25, 37.5, 50, 75 kVA... so round up.
Assumptions
- Single-phase transformer; three-phase sizing divides by √3 in the current formulas.
- Load is steady; motor starting inrush is a separate check.
Limitations
- Does not cover inrush/energization protection (NEC 450 rules apply).
- Ambient temperature and altitude derating for dry-type units is not applied.
- Harmonic-rich loads (K-factor) need specially rated transformers.
Frequently asked questions
What size transformer for a 10 kW load?
At PF 0.9 with 25% margin: 10/0.9 × 1.25 = 13.9 kVA → the standard 15 kVA unit.
Why are transformers rated in kVA?
Transformer heating comes from copper loss (I²R) and core loss, both driven by voltage and current magnitude — not by the load's phase angle. kVA captures that regardless of PF.