HVAC & Climate · Engineering calculator

Airflow / ACH Calculator

Enter room volume and target air changes per hour to get the required airflow in CFM, L/s and m³/h — or verify the ACH an existing fan delivers.

Open calculator
Engineering calculatorAirflow / ACH Calculator
Airflow / ACH Calculator inputs

Floor area × ceiling height.

Last updated: 2026-09-15

How the calculation works

  • One air change replaces the full room volume once; per minute that is volume/60, multiplied by the ACH target.
  • The result is shown in CFM, litres per second and cubic metres per hour for international fans.

Worked example

A 10 × 12 ft bathroom with 8 ft ceilings = 960 ft³. At 8 ACH: 960 × 8 / 60 = 128 CFM. The next standard fan size is 130 CFM — or run a 100 CFM fan slightly longer after showers.

Interpreting the result

The ACH target depends on the room's job: bathrooms and kitchens need high rates to remove moisture and odors quickly; bedrooms need moderate rates for air quality; whole-house ventilation runs at a low continuous rate. Exceeding the target wastes heating and cooling energy, so pick the target for the room type, not the maximum.

Assumptions

  • Well-mixed room air — real rooms stratify, and effective ventilation is lower than the theoretical value.
  • Fan rating at typical static pressure; real flow drops with ducting resistance.

Limitations

  • Does not account for duct losses, backdraft dampers or filter loading.
  • Codes (IMC/ASHRAE 62.2) may specify airflow directly rather than ACH — check local requirements.

Required airflow (CFM) by room volume and air changes per hour

Each cell is the calculator's result for that room volume and air-change target.

Room volume4 ACH6 ACH8 ACH10 ACH12 ACH
300 ft³2030405060
500 ft³33506783100
1,000 ft³67100133167200
1,500 ft³100150200250300
2,000 ft³133200267333400
3,000 ft³200300400500600

CFM = volume (ft³) × ACH ÷ 60. Round up to the next fan size that is available.

Common bathroom sizes at 8 air changes per hour (8 ft ceiling)

RoomVolume (ft³)Airflow (CFM)Airflow (L/s)
5 × 8 ft3204320
6 × 9 ft4325827
8 × 10 ft6408540
10 × 12 ft96012860
12 × 15 ft1,44019291

Worked scenario: an exhaust fan for a 5 × 8 ft bathroom

A 5 × 8 ft bathroom with an 8 ft ceiling holds 320 ft³. At 8 air changes per hour the calculator returns 42.7 CFM (20.1 L/s). Fans are sold in standard sizes, so the practical choice is the next size up.

Small-bathroom fans are commonly sold at 50 CFM, which matches the intermittent bathroom exhaust minimum in ASHRAE Standard 62.2. Check which edition your local code has adopted before relying on a single figure.

Mistakes that make the answer wrong

  • Using floor area instead of volume. Ceiling height multiplies the airflow you need.
  • Trusting the label rating. Ducts, elbows and a roof cap add resistance, and an installed fan delivers less than its free-air rating.
  • Mixing up ACH with CFM per square foot. They are different ways of stating a ventilation requirement and are not interchangeable.
  • Sizing exhaust without make-up air. In a tight house a strong exhaust fan can starve itself; the calculator sizes the exhaust only.

Frequently asked questions

How many CFM do I need for a bathroom?

The common rule is 1 CFM per ft² of floor area, which for a standard bathroom equals about 8 ACH. A 10 × 10 bathroom needs ~100 CFM.

What ACH should a bedroom have?

5–6 ACH with the door closed is a common target for air quality; whole-house continuous ventilation is much lower, around 0.35 ACH.